Critical severity · published May 14, 2019
CVE-2019-6572
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1…
9.1
CVSS
2.7%
EPSS
No
On KEV
Description
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Confidentiality
High
Integrity
High
Availability
None
Scope
Unchanged
Exploitation
Is it being used?
Exploit prediction (EPSS)2.7% · higher than 86% of CVEs
Exploited in the wildNo evidence yet
CISA KEVNot listed
Ransomware campaign useNot known
Affected products
Which versions
SH
Simatic Hmi MP Firmware · Siemens
All versions, or not specified · source: NVD
SH
Simatic Hmi OP Firmware · Siemens
All versions, or not specified · source: NVD
SH
Simatic Hmi TP Firmware · Siemens
All versions, or not specified · source: NVD
SW
Simatic Wincc (tia Portal) · Siemens
before 15.1 · source: NVD
SW
Simatic Wincc Runtime · Siemens
before 15.1; before 15.1 · source: NVD
Affected product
SH
Simatic Hmi Comfort Outdoor Panels Firmware
Siemens
More from Simatic Hmi Comfort Outdoor Panels Firmware
8.8
CVE-2018-13814
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V14), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V14), SIMATIC HMI KTP…
8.1
CVE-2018-13813
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update…
7.5
CVE-2019-6575
A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl
7.5
CVE-2019-6568
The webserver of the affected devices contains a vulnerability that may lead to a denial of service condition
7.5
CVE-2018-13812
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update…